S-shaped heat dissipation duct
Quality first, attentive service
S-shaped heat dissipation duct
Quality first, attentive service
The S-type steam heater (heat dissipation pipe) is a standard model of heat dissipation pipe, suitable for steam heating systems. As its inlet and outlet joints are located on both sides of the pipe, curved pipes are used to eliminate stress caused by thermal expansion and other reasons.
The S-type steam heater has various combinations of different surface tube lengths, tube numbers, row numbers, and fin spacing, with a total of 765 sizes and specifications.
Number of surface tubes |
B (mm) |
Basic parameters/ Row number/A (mm)/ Surface tube length |
24 | 30 | 36 | 42 | 48 | 54 | 60 | 66 | 72 | 78 | 84 | 90 | 96 | 102 | 108 | 114 | 120 | ||
830 | 980 | 1130 | 1280 | 1430 | 1580 | 1730 | 1880 | 2030 | 2180 | 2330 | 2480 | 2630 | 2780 | 2930 | 3080 | 3230 | |||||
12 | 530 |
Heat dissipation area(m²) Wind area(m²) Ventilation net cross-sectional area (m²) Inlet and outlet pipe joint (inch) Inlet and outlet pipe joint (inch) Net weight (KG) Net weight (KG) |
2 1 or 2 1 or 2 1 2 1 2 |
9 0.26 0.144 2 2 29.1 37 |
11.25 0.325 0.18 2 2 32.8 42.5 |
13.5 0.39 0.216 2 2 36.5 48 |
5.75 0.455 0.252 2 2 40.2 53.5 |
18 0.52 0.288 2 2 43.9 59 |
20.25 0.585 0.324 2 2 47.6 64.5 |
22.5 0.65 0.36 2 2 51.3 70 |
24.75 0.715 0.396 2 5/2 55 75.5 |
27 0.78 0.432 2 5/2 58.7 81.1 |
29.25 0.845 0.468 2 5/2 62.4 86.5 |
31.5 0.91 0.504 2 5/2 66.01 92 |
33.75 0.975 0.54 2 5/2 69.8 97.5 |
36 1.04 0.576 2 5/2 73.5 103 |
38.25 1.105 0.612 2 5/2 77.5 108.5 |
40.5 1.17 0.648 5/2 5/2 80.9 114 |
42.75 1.235 0.648 5/2 5/2 84.6 119.5 |
45 1.3 0.72 5/2 5/2 88.3 125 |
|
15 | 636 |
Heat dissipation area(m²) Wind area(m²) Ventilation net cross-sectional area (m²) Inlet and outlet pipe joint (inch) Inlet and outlet pipe joint (inch) Net weight (KG) Net weight (KG) |
2 1 or 2 1 or 2 1 2 1 2 |
11.25 0.325 0.18 2 2 34 43 |
14.06 0.406 0.225 2 2 38.3 50 |
16.88 0.488 0.27 2 2 42.6 57 |
19.68 0.569 0.315 2 2 46.9 64 |
22.5 0.65 0.36 2 2 51.2 71 |
25.31 0.731 0.405 2 2 55.5 78 |
28.13 0.812 0.45 2 2 59.8 85 |
30.94 0.894 0.495 2 5/2 64.1 92 |
33.75 0.975 0.54 2 5/2 68.4 99 |
36.56 1.056 0.585 2 5/2 72.7 106 |
39.38 1.137 0.63 2 5/2 77 113 |
42.19 1.219 0.675 5/2 5/2 81.3 120 |
45 1.3 0.72 5/2 5/2 85.6 127 |
47.81 1.381 0.765 5/2 5/2 89.9 134 |
50.63 1.462 0.81 5/2 5/2 94.2 141 |
53.44 1.544 0.855 5/2 5/2 98.5 148 |
56.25 1.625 0.9 5/2 5/2 102.8 155 |
|
18 | 742 |
Heat dissipation area(m²) Wind area(m²) Ventilation net cross-sectional area (m²) Inlet and outlet pipe joint (inch) Inlet and outlet pipe joint (inch) Net weight (KG) Net weight (KG) |
2 1 or 2 1 or 2 1 2 1 2 |
13.5 0.39 0.216 2 2 39 50 |
16.88 0.488 0.27 2 2 44 57.8 |
20.25 0.586 0.324 2 2 49 65.6 |
23.63 0.684 0.378 2 2 54 73.4 |
27 0.782 0.432 2 5/2 59 81.2 |
30.38 0.88 0.486 2 5/2 64 89 |
33.75 0.978 0.54 2 5/2 69 96.8 |
37.13 1.076 0.594 2 5/2 74 104.6 |
40.5 1.174 0.648 5/2 5/2 79 112.4 |
43.88 1.272 0.702 5/2 5/2 84 120.2 |
47.25 1.37 0.756 5/2 5/2 89 128 |
50.63 1.068 0.81 5/2 5/2 94 135.8 |
54 1.566 0.864 5/2 5/2 99 143.6 |
57.38 1.664 0.918 5/2 5/2 104 151.4 |
60.75 1.762 0.972 5/2 5/2 109 159.2 |
64.13 1.86 1.026 5/2 5/2 114 167 |
67.5 1.958 1.08 5/2 5/2 119 174.8 |
|
21 | 843 |
Heat dissipation area(m²) Wind area(m²) Ventilation net cross-sectional area (m²) Inlet and outlet pipe joint (inch) Inlet and outlet pipe joint (inch) Net weight (KG) Net weight (KG) |
2 1 or 2 1 or 2 1 2 1 2 |
15.75 0.455 0.252 5/2 5/2 43 57 |
19.69 0.568 0.315 5/2 5/2 48.5 66 |
23.63 0.681 0.378 5/2 5/2 54 75 |
27.56 0.794 0.441 5/2 5/2 59.5 84 |
31.5 0.907 0.504 5/2 5/2 65 93 |
35.44 1.02 0.567 5/2 5/2 70.5 102 |
39.38 1.133 0.63 5/2 5/2 76 111.0 |
43.31 1.246 0.693 5/2 5/2 81.5 120 |
47.35 1.359 0.756 5/2 5/2 87 129 |
51.29 1.472 0.819 5/2 5/2 92.5 138 |
55.13 1.585 0.882 5/2 5/2 98 147 |
59.06 1.698 0.945 5/2 5/2 103.5 156 |
63 1.811 1.008 5/2 5/2 109 165 |
66.94 1.924 1.071 5/2 5/2 14.5 174 |
70.88 2.037 1.134 5/2 5/2 120 183 |
74.81 2.15 1.197 5/2 5/2 25.5 192 |
78.75 2.263 1.26 5/2 5/2 131 201 |
|
24 | 954 |
Heat dissipation area(m²) Wind area(m²) Ventilation net cross-sectional area (m²) Inlet and outlet pipe joint (inch) Inlet and outlet pipe joint (inch) Net weight (KG) Net weight (KG) |
2 1 or 2 1 or 2 1 2 1 2 |
18 0.52 0.288 5/2 5/2 50 64 |
22.5 0.65 0.36 5/2 5/2 56 74 |
27 0.78 0.432 5/2 5/2 62 84 |
31.5 0.91 0.504 5/2 5/2 68 94 |
36 1.04 0.576 5/2 5/2 74 104 |
40.5 1.17 0.648 5/2 5/2 80 114 |
45 1.3 0.72 5/2 5/2 86 124 |
49.5 1.43 0.792 5/2 5/2 92 134 |
54 1.56 0.864 5/2 5/2 98 144 |
58.5 1.69 0.936 5/2 5/2 104 154 |
63 1.83 1.008 5/2 5/2 110 164 |
67.5 1.95 1.08 5/2 5/2 116 174 |
72 2.08 1.152 5/2 5/2 122 184 |
76.5 2.21 1.224 5/2 5/2 128 194 |
81 2.34 1.296 5/2 5/2 134 204 |
85.5 2.47 1.368 5/2 5/2 140 214 |
90 2.6 1.44 5/2 5/2 146 224 |